AES MODELS
RM3601
3801
MODULEBOARDREPLACEMENT
q
D U O- THERM
Refrigerator
Bulletin
R59/7A
May 1987
NOTE:
Please take full consideration of the following
information BEFORE replacing module boards due
to faulty 12 volt cooling operation.
This Bulletin clarifies the 12 volt DC start-up and cooling
operation.
Each time the tag line is energized and 12 volt cooling is
selected, the module board must receive approximately 13.6
volts for about 40 or more seconds.
At that time the
unit
will engage
the 12
volt heating element. If
the
initial
required
13.6
volts is not achieved (due
to demands of other 12
volt devices) the AES will
not
switch to 12 volt
operation,
and will operate
instead on L.P. gas until the
13.6 volt threshold is reached.
If during 12 volt cooling,
supply voltage should drop below
approximately 11.6 volts (FIG. 2), the DC cooling will shut
down and the AES system will go into a 25 minute delay (FIG.
3). This allows the supply voltage to re-establish itself.
To view the delay, push the button identified with a question
mark
q and the clock indicator light
a
will come on.
NOTE:
If 13.6 volts is not recovered during the delay the AES
system will then switch to gas operation until the supply voltage
recovers.
If during the 25 minute delay the 13.6 threshold
voltage is recovered, the delay will be deleted and 12 volts DC
cooling will resume.
FIG.
1
FIG. 2
AES CONTROL PANEL ON REFRIGERATOR
FIG. 3
As with all AES refrigerators, minimum voltage for any
operation is 10.5 volts DC at the terminal block.
FIG. 4
IGN
LOCK
---
---
+
1
A-l1-9
84